NECwire

What size wire for 15 amps?

14 AWG copper or 12 AWG aluminum with 75 °C terminations, by NEC Table 310.16 at 30 °C with no more than three current-carrying conductors. General lighting and receptacle circuits; 14 AWG copper is the smallest size 240.4(D) allows on a 15 A breaker.

Minimum conductor size
Minimum size · copper14AWGFITS75 °C insulation on 75 °C terminations · needs 15 A at 30 °C ambient with 3 current-carrying conductors · NEC 2023 Table 310.16

The load, or the breaker rating you must feed

Conductor
Continuous load
Table 310.16 ampacity, 14 AWG at 75 °CNEC 2023 Table 310.16, identical to 2017 Table 310.15(B)(16)
20 A
After correction and adjustment× 1.00 for 30 °C (NEC 2023 Table 310.15(B)(1)(1)) × 1.00 for 3 conductors (NEC 2023 Table 310.15(C)(1))
20.0 A
Termination cap, 110.14(C) at 75 °CCircuits > 100 A or larger than 1 AWG use the 75 °C column
20 A
240.4(D) small-conductor limit for 14 AWGOvercurrent protection may not exceed this after correction factors
15 A
Usable ampacitythe smallest of the three above
15.0 A

Ampacity from NEC 2023 Table 310.16 (identical to 2017 Table 310.15(B)(16)), corrected for ambient and conductor count, capped by the termination rating (110.14(C)) and the small-conductor limits of 240.4(D). Equipment listings, conductor markings and local amendments govern; a licensed electrician makes the final call.

Insulation rating
Termination rating

30 °C is the table base; attics and rooftops run hotter

In the same raceway or cable; 3 or fewer needs no adjustment

Adds a voltage-drop check against the 3 % note

For the drop check

Phase

Nothing typed leaves the browser; the inputs live only in the page address.

Every column for 15 A

Conductor and terminationsSizeUsable ampacityWhy
Copper, 60 °C (TW, UF; or unmarked equipment ≤ 100 A)14 AWG15 A240.4(D) limit 15 A
Copper, 75 °C (THW, THWN, XHHW; marked 75 °C terminations)14 AWG15 A240.4(D) limit 15 A
Copper, 90 °C insulation on 75 °C terminations (THHN)14 AWG15 A240.4(D) limit 15 A
Aluminum, 75 °C12 AWG15 A240.4(D) limit 15 A
Aluminum, 90 °C insulation on 75 °C terminations (XHHW-2)12 AWG15 A240.4(D) limit 15 A
Copper, 75 °C, continuous load at 80 % of the breaker (12 A × 1.25)14 AWG15 A210.19(A)(1): a continuous load is sized at 125 %

How far it can run

K-factor method at 80 % load (12 A), single-phase, one-way length for a 3 % drop (an informational note, not a requirement), and the drop at 100 ft.

ConductorVoltage3 % reached atDrop at 100 ft
14 AWG copper120 V48 ft6.3 %open
14 AWG copper240 V96 ft3.1 %open
12 AWG aluminum120 V46 ft6.5 %open
12 AWG aluminum240 V92 ft3.2 %open

Questions people ask

What size wire do I need for a 15 amp breaker?
With 75 °C terminations, 14 AWG copper or 12 AWG aluminum (NEC Table 310.16). With 60 °C terminations, 14 AWG copper. Long runs may need a size up for voltage drop.
Can I use 14 AWG THHN copper on 15 amps?
Yes: 14 AWG is the answer at both 75 °C and 90 °C, because the 90 °C column may only be used for derating; the termination (110.14(C)) caps the conductor at its 75 °C value.
How far can 14 AWG copper run on a 15 amp circuit?
At 80 % load (12 A) and the 3 % informational note, about 48 ft one-way at 120 V and 96 ft at 240 V by the K-factor method. Beyond that, go up a size.