What size wire for 300 amps?
350 kcmil copper or 500 kcmil aluminum with 75 °C terminations, by NEC Table 310.16 at 30 °C with no more than three current-carrying conductors. Commercial and light-industrial feeders; consider parallel sets.
The load, or the breaker rating you must feed
- Table 310.16 ampacity, 350 kcmil at 75 °CNEC 2023 Table 310.16, identical to 2017 Table 310.15(B)(16)
- 310 A
- After correction and adjustment× 1.00 for 30 °C (NEC 2023 Table 310.15(B)(1)(1)) × 1.00 for 3 conductors (NEC 2023 Table 310.15(C)(1))
- 310.0 A
- Termination cap, 110.14(C) at 75 °CCircuits > 100 A or larger than 1 AWG use the 75 °C column
- 310 A
- Usable ampacitythe smallest of the three above
- 310.0 A
Ampacity from NEC 2023 Table 310.16 (identical to 2017 Table 310.15(B)(16)), corrected for ambient and conductor count, capped by the termination rating (110.14(C)) and the small-conductor limits of 240.4(D). Equipment listings, conductor markings and local amendments govern; a licensed electrician makes the final call.
30 °C is the table base; attics and rooftops run hotter
In the same raceway or cable; 3 or fewer needs no adjustment
Adds a voltage-drop check against the 3 % note
For the drop check
Nothing typed leaves the browser; the inputs live only in the page address.
Every column for 300 A
| Conductor and terminations | Size | Usable ampacity | Why |
|---|---|---|---|
| Copper, 60 °C (TW, UF; or unmarked equipment ≤ 100 A) | 500 kcmil | 320 A | Table 310.16, 320 A |
| Copper, 75 °C (THW, THWN, XHHW; marked 75 °C terminations) | 350 kcmil | 310 A | Table 310.16, 310 A |
| Copper, 90 °C insulation on 75 °C terminations (THHN) | 350 kcmil | 310 A | capped at the 75 °C column (110.14(C)) |
| Aluminum, 75 °C | 500 kcmil | 310 A | Table 310.16, 310 A |
| Aluminum, 90 °C insulation on 75 °C terminations (XHHW-2) | 500 kcmil | 310 A | capped at the 75 °C column (110.14(C)) |
| Copper, 75 °C, continuous load at 80 % of the breaker (240 A × 1.25) | 350 kcmil | 310 A | 210.19(A)(1): a continuous load is sized at 125 % |
How far it can run
K-factor method at 80 % load (240 A), single-phase, one-way length for a 3 % drop (an informational note, not a requirement), and the drop at 100 ft.
Questions people ask
- What size wire do I need for a 300 amp breaker?
- With 75 °C terminations, 350 kcmil copper or 500 kcmil aluminum (NEC Table 310.16). With 60 °C terminations, 500 kcmil copper. Long runs may need a size up for voltage drop.
- Can I use 350 kcmil THHN copper on 300 amps?
- Yes: 350 kcmil is the answer at both 75 °C and 90 °C, because the 90 °C column may only be used for derating; the termination (110.14(C)) caps the conductor at its 75 °C value.
- How far can 350 kcmil copper run on a 300 amp circuit?
- At 80 % load (240 A) and the 3 % informational note, about 203 ft one-way at 120 V and 407 ft at 240 V by the K-factor method. Beyond that, go up a size.